Customisations available
Lead times
Dedicated Sertus delivery
Up to 40 mm overall construction tolerance
Engineered SLD aperture
Construction-stage fall protection
Sealed for shaft air leakage testing to BS EN 1026:2016
Pre-assembled temporary infill panel
Developed and tested with the Sertus SLD
Accommodates up to 40 mm overall construction tolerance in solid construction smoke shaft openings
Provides a consistent, precisely formed aperture for installation of the Sertus SLD
Pre-assembled temporary infill provides fall protection during construction
Sealed infill enables smoke shaft air leakage testing before SLD installation
Provision for first-fix cabling ahead of SLD installation
Engineered and tested for use with the Sertus SLD, supporting a consistent installation
Available to suit the complete Sertus SLD size range
Suitable for SLD free areas up to 1.03 m²
Powder-coated steel and lightweight calcium silicate fireboard construction
Supplied with pre-assembled temporary infill panel
Anchor bolts and fire-tested sealant supplied
Sertus ShaftPanel™ has been developed and tested for use with the Sertus Shaft Louvre Damper (SLD). Fire performance classification and certification relate to the tested SLD assembly, rather than ShaftPanel as a standalone product.
Fire Performance & Compatibility
Fire tested to BS EN 1366-10:2011+A1:2017
Classified to BS EN 13501-4:2016
SLD certified to BS EN 12101-8:2011
Fire resistance classification: EIS 120
Temporary Infill Protection & Testing
Load tested to BS EN 6180 (Approved Document K)
Impact tested to BS EN 13049
Air leakage tested to BS EN 1026:2016
Patent pending – 2607945.9

Solid construction smoke shafts (masonry and concrete)
Sertus Shaft Louvre Damper (SLD)
Up to 40 mm overall
EIS 120 (tested SLD assembly)
BS EN 1366-10:2011+A1:2017 (with SLD)
BS EN 13501-4:2016 (SLD assembly)
BS EN 12101-8:2011 (SLD certification)
BS EN 6180 (Approved Document K)
BS EN 13049
BS EN 1026:2016
1.03 m²
Powder-coated steel and lightweight calcium silicate fireboard
Pre-assembled, removable panel with rubber seal
Temporary infill panel provides construction-stage fall protection
Anchor bolts supplied
Fire-tested sealant supplied
Provision for supply cables
Fire performance classification and certification relate to the tested Sertus SLD assembly and not to ShaftPanel™ as a standalone product. Refer to the SLD Technical Data Sheet for further information.
| For Damper Ref | ShaftPanel™ Ref | ShaftPanel™ Overall Size (mm) |
|---|---|---|
| SLD 30.40 | SSP 30.40 | 437 x 659 |
| SLD 30.45 | SSP 30.45 | 437 x 709 |
| SLD 30.50 | SSP 30.50 | 437 x 759 |
| SLD 30.55 | SSP 30.55 | 437 x 809 |
| SLD 30.60 | SSP 30.60 | 437 x 859 |
| SLD 30.65 | SSP 30.65 | 437 x 909 |
| SLD 30.70 | SSP 30.70 | 437 x 959 |
| SLD 30.75 | SSP 30.75 | 437 x 1009 |
| SLD 30.80 | SSP 30.80 | 437 x 1059 |
| SLD 30.85 | SSP 30.85 | 437 x 1109 |
| SLD 30.90 | SSP 30.90 | 437 x 1159 |
| SLD 30.95 | SSP 30.95 | 437 x 1209 |
| SLD 30.100 | SSP 30.100 | 437 x 1259 |
| SLD 30.105 | SSP 30.105 | 437 x 1309 |
| SLD 30.110 | SSP 30.110 | 437 x 1359 |
| SLD 30.115 | SSP 30.115 | 437 x 1409 |
| SLD 30.120 | SSP 30.120 | 437 x 1459 |
| SLD 30.125 | SSP 30.125 | 437 x 1509 |
| SLD 30.130 | SSP 30.130 | 437 x 1559 |
| SLD 30.135 | SSP 30.135 | 437 x 1609 |
| SLD 30.140 | SSP 30.140 | 437 x 1659 |
| SLD 30.145 | SSP 30.145 | 437 x 1709 |
| SLD 30.150 | SSP 30.150 | 437 x 1759 |
| SLD 30.155 | SSP 30.155 | 437 x 1809 |
| SLD 30.160 | SSP 30.160 | 437 x 1859 |
| SLD 30.165 | SSP 30.165 | 437 x 1909 |
| SLD 30.170 | SSP 30.170 | 437 x 1959 |
| SLD 30.175 | SSP 30.175 | 437 x 2009 |
| SLD 30.180 | SSP 30.180 | 437 x 2059 |
| SLD 30.185 | SSP 30.185 | 437 x 2109 |
| SLD 45.40 | SSP 45.40 | 587 x 659 |
| SLD 45.45 | SSP 45.45 | 587 x 709 |
| SLD 45.50 | SSP 45.50 | 587 x 759 |
| SLD 45.55 | SSP 45.55 | 587 x 809 |
| SLD 45.60 | SSP 45.60 | 587 x 859 |
| SLD 45.65 | SSP 45.65 | 587 x 909 |
| SLD 45.70 | SSP 45.70 | 587 x 959 |
| SLD 45.75 | SSP 45.75 | 587 x 1009 |
| SLD 45.80 | SSP 45.80 | 587 x 1059 |
| SLD 45.85 | SSP 45.85 | 587 x 1109 |
| SLD 45.90 | SSP 45.90 | 587 x 1159 |
| SLD 45.95 | SSP 45.95 | 587 x 1209 |
| SLD 45.100 | SSP 45.100 | 587 x 1259 |
| SLD 45.105 | SSP 45.105 | 587 x 1309 |
| SLD 45.110 | SSP 45.110 | 587 x 1359 |
| SLD 45.115 | SSP 45.115 | 587 x 1409 |
| SLD 45.120 | SSP 45.120 | 587 x 1459 |
| SLD 45.125 | SSP 45.125 | 587 x 1509 |
| SLD 45.130 | SSP 45.130 | 587 x 1559 |
| SLD 45.135 | SSP 45.135 | 587 x 1609 |
| SLD 45.140 | SSP 45.140 | 587 x 1659 |
| SLD 45.145 | SSP 45.145 | 587 x 1709 |
| SLD 45.150 | SSP 45.150 | 587 x 1759 |
| SLD 45.155 | SSP 45.155 | 587 x 1809 |
| SLD 45.160 | SSP 45.160 | 587 x 1859 |
| SLD 45.165 | SSP 45.165 | 587 x 1909 |
| SLD 45.170 | SSP 45.170 | 587 x 1959 |
| SLD 45.175 | SSP 45.175 | 587 x 2009 |
| SLD 45.180 | SSP 45.180 | 587 x 2059 |
| SLD 45.185 | SSP 45.185 | 587 x 2109 |
| SLD 60.40 | SSP 60.40 | 737 x 659 |
| SLD 60.45 | SSP 60.45 | 737 x 709 |
| SLD 60.50 | SSP 60.50 | 737 x 759 |
| SLD 60.55 | SSP 60.55 | 737 x 809 |
| SLD 60.60 | SSP 60.60 | 737 x 859 |
| SLD 60.65 | SSP 60.65 | 737 x 909 |
| SLD 60.70 | SSP 60.70 | 737 x 959 |
| SLD 60.75 | SSP 60.75 | 737 x 1009 |
| SLD 60.80 | SSP 60.80 | 737 x 1059 |
| SLD 60.85 | SSP 60.85 | 737 x 1109 |
| SLD 60.90 | SSP 60.90 | 737 x 1159 |
| SLD 60.95 | SSP 60.95 | 737 x 1209 |
| SLD 60.100 | SSP 60.100 | 737 x 1259 |
| SLD 60.105 | SSP 60.105 | 737 x 1309 |
| SLD 60.110 | SSP 60.110 | 737 x 1359 |
| SLD 60.115 | SSP 60.115 | 737 x 1409 |
| SLD 60.120 | SSP 60.120 | 737 x 1459 |
| SLD 60.125 | SSP 60.125 | 737 x 1509 |
| SLD 60.130 | SSP 60.130 | 737 x 1559 |
| SLD 60.135 | SSP 60.135 | 737 x 1609 |
| SLD 60.140 | SSP 60.140 | 737 x 1659 |
| SLD 60.145 | SSP 60.145 | 737 x 1709 |
| SLD 60.150 | SSP 60.150 | 737 x 1759 |
| SLD 60.155 | SSP 60.155 | 737 x 1809 |
| SLD 60.160 | SSP 60.160 | 737 x 1859 |
| SLD 60.165 | SSP 60.165 | 737 x 1909 |
| SLD 60.170 | SSP 60.170 | 737 x 1959 |
| SLD 60.175 | SSP 60.175 | 737 x 2009 |
| SLD 60.180 | SSP 60.180 | 737 x 2059 |
| SLD 60.185 | SSP 60.185 | 737 x 2109 |
| SLD 75.40 | SSP 75.40 | 887 x 659 |
| SLD 75.45 | SSP 75.45 | 887 x 709 |
| SLD 75.50 | SSP 75.50 | 887 x 759 |
| SLD 75.55 | SSP 75.55 | 887 x 809 |
| SLD 75.60 | SSP 75.60 | 887 x 859 |
| SLD 75.65 | SSP 75.65 | 887 x 909 |
| SLD 75.70 | SSP 75.70 | 887 x 959 |
| SLD 75.75 | SSP 75.75 | 887 x 1009 |
| SLD 75.80 | SSP 75.80 | 887 x 1059 |
| SLD 75.85 | SSP 75.85 | 887 x 1109 |
| SLD 75.90 | SSP 75.90 | 887 x 1159 |
| SLD 75.95 | SSP 75.95 | 887 x 1209 |
| SLD 75.100 | SSP 75.100 | 887 x 1259 |
| SLD 75.105 | SSP 75.105 | 887 x 1309 |
| SLD 75.110 | SSP 75.110 | 887 x 1359 |
| SLD 75.115 | SSP 75.115 | 887 x 1409 |
| SLD 75.120 | SSP 75.120 | 887 x 1459 |
| SLD 75.125 | SSP 75.125 | 887 x 1509 |
| SLD 75.130 | SSP 75.130 | 887 x 1559 |
| SLD 75.135 | SSP 75.135 | 887 x 1609 |
| SLD 75.140 | SSP 75.140 | 887 x 1659 |
| SLD 75.145 | SSP 75.145 | 887 x 1709 |
| SLD 75.150 | SSP 75.150 | 887 x 1759 |
| SLD 75.155 | SSP 75.155 | 887 x 1809 |
| SLD 75.160 | SSP 75.160 | 887 x 1859 |
| SLD 75.165 | SSP 75.165 | 887 x 1909 |
| SLD 75.170 | SSP 75.170 | 887 x 1959 |
| SLD 75.175 | SSP 75.175 | 887 x 2009 |
| SLD 75.180 | SSP 75.180 | 887 x 2059 |
| SLD 75.185 | SSP 75.185 | 887 x 2109 |
ShaftPanel™ accommodates construction tolerances in solid construction smoke shafts, providing the precise aperture required for installation of the Sertus Shaft Louvre Damper (SLD). This helps reduce remedial works and simplifies on-site coordination.
ShaftPanel™ accommodates up to 40 mm overall construction tolerance.
Yes. The pre-assembled temporary infill panel provides fall protection during construction, subject to the tested installation arrangement.
Smoke shafts should be air leakage tested before the SLD is installed. ShaftPanel™ features a temporary infill with an integrated rubber seal, removing the need to seal damper openings with temporary materials. Tested to BS EN 1026:2016, the infill has a known leakage rate, allowing contractors to account for this when assessing overall shaft leakage.
ShaftPanel™ has been developed and tested specifically for use with the Sertus Shaft Louvre Damper (SLD).
ShaftPanel™ helps main contractors reduce the risk of remedial works, unnecessary temporary works and programme disruption. By providing a defined opening early in construction, it supports safer working, simpler coordination and more predictable project delivery.
The main contractor typically retains responsibility for shaft construction and performance, subject to agreed project responsibilities. ShaftPanel™ provides a defined installation interface for the Sertus SLD, helping simplify coordination between the main contractor and smoke control specialist.
A prepared, accurate opening allows installers to fit the Sertus SLD with fewer site adjustments, return visits and unnecessary disruption.
While ShaftPanel™ adds a product cost, it can reduce expenditure on temporary grilles, remedial works, repeat visits and coordination. The overall installed cost should be considered, rather than the product price alone.
ShaftPanel™ reduces uncertainty around opening dimensions, temporary protection and final damper installation, helping avoid remedial works and programme delays.
Yes. ShaftPanel™ includes provision for SLD supply cables to be installed during first fix, ahead of final damper installation.
ShaftPanel™ is designed for installation into solid construction smoke shafts, with a C-stud and plasterboard lining forming part of the installation arrangement. Refer to the Sertus technical installation guidance for the required lining specification and installation details.
No. ShaftPanel™ is supplied with precise internal dimensions to accommodate the Sertus SLD, eliminating the need for additional internal lining before damper installation.
As early as possible, ideally before structural openings are finalised, to coordinate SLD sizes, opening requirements and the installation programme.
No. ShaftPanel™ has been fire tested with the Sertus SLD without a finished wall. This gives building designers flexibility to specify the final wall finish without affecting the tested arrangement, provided the installation follows the approved technical details.